Illustrative images

Construction Characteristics

Armored Substation with manufactured modules in BWG 14:12 steel galvanized at plant, protection grade IP-30, painted by electrostatic process using powder paint based on epoxy gray RAL7032. The rails are made of electrolytic copper with 99.9% purity and coated where necessary by heat-contractible insulation.


PRODUCT TESTED IN CEPEL, IPT, FURB and LABELO

 

standard Applicable NBR IEC 62271-200 | NBR IEC 60694
Rated Voltage (Ur) 17,5kV 24kV 36kV
Insulation level (NI) 95kV 125kV 175kV
Rated Current (Ir) 630A / 1250A
Current Short Term (Ik/tk) 25kA/1s | 31,5kA/1s | 40kA/1s
Internal arc classification AFLR
Degree of Protection IP-40 | IP-44 | IP-54 (sob consulta)
Loss of Continuity of Service / Class LSC2B / PM
Predominant color gray MUNSELL N6,5
Operating Temperature -5°C à +40°C
Installation Type sheltered | open space
Maximum Altitude Relative to Sea Level ≤ 1000m